Running Watts vs Starting Watts for Generator Planning

Room mid-renovation with paint rollers, flooring planks and roofing shingles

Last updated

Running watts are continuous draw. Additional starting watts are the extra surge above running watts while a motor starts; total starting watts = running + additional. Plan with: sum of running watts + the single largest additional starting watts, assuming one motor starts at a time.

Generator worksheets list two numbers per appliance, and the labels are easy to misread. Getting the arithmetic right avoids buying a generator that stalls when a compressor kicks on — or one far bigger than needed.

Run the numbers with the Generator Wattage Planner.

The three numbers

Example figures — use your nameplate or manual

ApplianceRunning WAdditional start WTotal start W
Refrigerator (example)7001,5002,200
Sump pump (example)8001,3002,100
LED lights ×6 (example)60060

Worked example

Running load = 700 + 800 + 60 = 1,560 W. Largest additional start = 1,500 W, so the one-start peak = 3,060 W. If both motors started at the same instant: 1,560 + 1,500 + 1,300 = 4,360 W. Adding total starting watts for everything (2,200 + 2,100 + 60 = 4,360) happens to match here only because the lights add nothing — with more resistive loads that shortcut double-counts.

Safety essentials

  • Run portable generators outdoors only, at least 20 ft from doors, windows and vents, and never in an attached garage (NFPA).
  • Install battery or battery-backup CO alarms (CPSC, USFA).
  • Do not backfeed through an outlet; connecting to house wiring requires a properly rated transfer switch installed by a qualified electrician (NFPA).
  • Let the engine cool before refuelling.

Common mistakes

  • Treating additional starting watts as total starting watts
  • Ignoring that output can differ by fuel type
  • Assuming a worksheet total is an installation size

Assumptions and limitations

Motor inrush varies with the motor and conditions, soft starters reduce it, and 240 V generators split loads across two 120 V legs. Standby installations must be sized and installed by a licensed electrician.