Room-by-Room CFM Planner

Build a room airflow schedule for up to six rooms in one of two clearly separate modes. Air-change mode turns room volume and an air-changes-per-hour target into CFM — useful for ventilation or air-cleaning goals. Cooling-supply mode turns each room's sensible cooling load from a load calculation into supply CFM using the standard-air sensible heat equation. The two answers measure different things and are never mixed. Dimensions can be in feet or meters; output is in cubic feet per minute.

Room mid-renovation with paint rollers, flooring planks and roofing shingles

How do I calculate CFM for a room?

It depends on the goal. For an air-change target, CFM = length × width × height (ft³) × ACH ÷ 60 — a 14 × 12 × 8 ft room at 4 ACH needs 1,344 × 4 ÷ 60 = 89.6 CFM. For cooling supply, CFM = sensible load ÷ (1.08 × ΔT) — a 4,000 BTU/h room at a 20 °F difference needs about 185 CFM. The two answers are not interchangeable.

Key takeaways

  • Mode A answers 'how often is the room's air replaced'; mode B answers 'how much supply air removes this heat'.
  • 1.08 = 0.075 lb/ft³ × 60 min/h × 0.24 BTU/lb·°F for standard air; it changes at altitude.
  • Duct sizes come from a Manual D design, not from CFM alone.

Enter your details

Setup

Your chosen target — e.g. from an air-cleaner or ventilation goal. It is not a code value.

Room 1
Room 2
Room 3

Estimated result

Total air-change airflow

208 CFM

3 rooms, 3,120 ft³

Calculation breakdown

Formula
CFM = ft³ × ACH ÷ 60
Total volume
3,120 ft³
ACH target
4
Total air-change airflow
208 CFM
  • Air-change airflow is not HVAC supply airflow. Use mode B with load-calculation figures to plan cooling supply.

Room airflow schedule

RoomVolume (ft³)ACHCFM
Room 11,344490
Room 21,056470
Room 3720448
Total3,120208

Your result is an estimate based on the information entered.

Calculated in your browser

This calculator runs locally; your exact figures are not sent to our servers. Anonymous usage events (calculator name, field names, rounded value ranges) are recorded by Google Analytics — see the privacy policy.

How to use this calculator

  1. Choose mode A for an air-change target or mode B when you have room cooling loads.
  2. Select how many rooms, then enter each room's dimensions in one unit.
  3. Enter the ACH target (A) or each sensible load and the supply ΔT (B).
  4. Print or download the room schedule for your contractor.

What each input means

InputWhat it means
ACHAir changes per hour you want to achieve — a target you choose, not a code figure.
Sensible cooling loadPer-room sensible BTU/h from a Manual J or equivalent report.
ΔTDifference between room air and supply air temperature in °F.

Formula used

A: CFM = (L × W × H in ft³) × ACH ÷ 60

B: CFM = Sensible BTU/h ÷ (1.08 × ΔT °F)

Meters are converted at 1 m = 3.28084 ft before volume is calculated.

Worked example

Three rooms — 14 × 12 × 8, 12 × 11 × 8 and 10 × 9 × 8 ft — hold 1,344 + 1,056 + 720 = 3,120 ft³. At 4 ACH: 89.6 + 70.4 + 48.0 = 208 CFM. In cooling mode with sensible loads of 4,000, 3,000 and 2,000 BTU/h at ΔT 20 °F (divisor 21.6): 185.2 + 138.9 + 92.6 ≈ 417 CFM.

Common mistakes to avoid

  • Using ACH airflow to size supply registers

    Ventilation airflow says nothing about how much heat a room gains.

  • Entering total load instead of sensible

    Latent (moisture) load is not removed by the 1.08 equation; using total load overstates CFM.

  • Mixing meters and feet

    Pick one dimension unit for all rooms — the tool converts meters to cubic feet for you.

When the estimate may differ from reality

Measured airflow at a register often differs from the schedule: duct leakage, fittings, filter loading and blower speed change what arrives. Ventilation codes may also require specific rates that differ from your chosen ACH target.

Assumptions and limitations

What this calculator assumes

  • Rectangular rooms with flat ceilings.
  • Standard air density (sea level, about 70 °F) for the 1.08 constant.
  • Loads entered are already calculated by a recognised method.

What it does not account for

  • Does not calculate cooling loads, ventilation code requirements or duct sizes.
  • High-altitude homes need a corrected air-density constant.

Frequently asked questions

What ACH should I use?
It depends on the purpose — an air cleaner's rating, a designer's ventilation plan or a specific guideline. The calculator leaves ACH editable rather than suggesting a universal number.
Can I turn CFM into duct size here?
No. Duct sizing depends on friction rate, fittings and blower performance, which Manual D covers. A CFM figure alone is not enough.